Energy Monitoring Current Sensors (Current Transformer)


  • UL Recognized
  • Precision burden resistor
  • Epoxy encapsulated housing


SCT-0750 Energy Monitoring Current Sensors

Current Transformer with 0.75 inch opening measures AC current passing through the center

This current transformer is suitable for all devices and applications requiring output of 0.333 Volt at a 100% current. In the 0.75 inch series all devices have a burden resistor except the 0-200A device which does not have a burden resistor and its output voltage is clamped to 22 Volts.

Note: Only use CTs with burden resistors for Ringdale Energy Monitor Device.
Dimensions


Part No. Rated Current (Amps) Dimension (inches)
A B C D E
00-11-0750-0000*0-200
00-11-0750-00055
00-11-0750-001010
00-11-0750-001515
00-11-0750-002020
00-11-0750-002525
00-11-0750-003030
00-11-0750-005050
00-11-0750-006060
00-11-0750-007070
00-11-0750-0100100
00-11-0750-0150150
00-11-0750-0200200
*Products with -0000 have no burden resistor.
2.00 2.10 0.61 0.75 0.75

The following table shows the output voltage versus the percentage of 'Rated Current' (see table above).

Output vs Percentage of Rated Current


Part Number: 00-11-0750-0000


Technical Information

Output:0.333 Volts at rated current
Accuracy:1%
Phase Angle:<2° for current >70Amps.
Rated Accuracy:at 10% to 130%
Leads:8 ft, twisted pair, 22 AWG
Part Number:00-11-0750-0000

Caution! All specifications published herein are subject to change without notice. See website ActiveLED.com for Terms and Conditions of use of the website and the information provided herein. See Ringdale website on www.ringdale-technology.com for Terms and Condtions of Sale and Service.

+1-833-850-7097
+44 (0)844 264 1570